LG AMNW09GDBR0 Yükleme Rehberi

Kategori
Split sistem klimalar
Tip
Yükleme Rehberi

Bu kılavuz aynı zamanda aşağıdakiler için de uygundur:

P/NO : MFL67737203
www.lg.com
INSTALLATION MANUAL
AIR CONDITIONER
• Please read this installation manual completely before installing the product.
• Installation work must be performed in accordance with the national wiring
standards by authorized personnel only.
• Please retain this installation manual for future reference after reading it
thoroughly.
TYPE : WALL MOUNTED
ENGLISH
TÜRKÇE
• Do not cool excessively indoors. This may be harmful for your health and may consume more
electricity.
• Block sunlight with blinds or curtains while you are operating the air conditioner.
• Keep doors or windows closed tightly while you are operating the air conditioner.
• Adjust the direction of the air flow vertically or horizontally to circulate indoor air.
• Speed up the fan to cool or warm indoor air quickly, in a short period of time.
• Open windows regularly for ventilation as the indoor air quality may deteriorate if the air condi-
tioner is used for many hours.
• Clean the air filter once every 2 weeks. Dust and impurities collected in the air filter may block the
air flow or weaken the cooling / dehumidifying functions.
For your records
Staple your receipt to this page in case you need it to prove the date of purchase or for warranty
purposes. Write the model number and the serial number here:
Model number :
Serial number :
You can find them on a label on the side of each unit.
Dealer’s name :
Date of purchase :
Here are some tips that will help you minimize the power consumption when you use the air
conditioner. You can use your air conditioner more efficiently by referring to the instructions
below:
TIPS FOR SAVING ENERGY
TIPS FOR SAVING ENERGY
2
ENGLISH
3
IMPORTANT SAFETY INSTRUCTIONS
READ ALL INSTRUCTIONS BEFORE USING THE APPLIANCE.
Always comply with the following precautions to avoid dangerous situations and ensure peak
performance of your product
LG Electronics is not responsible for Product`s malfunction or damage which caused by improper
installation or misuse of operation guide.
WARNING
It can result in serious injury or death when the directions are ignored
CAUTION
It can result in minor injury or product damage when the directions are ignored
WARNING
• Installation or repairs made by unqualified persons can result in hazards to you and others.
• Installation MUST conform with local building codes or, in the absence of local codes, with
the Nation Electrical Code NFPA 70/ANSI C1-1003 or current edition and Canadian Electrical
Code Part1 CSA C.22.1.
• The information contained in the manual is intended for use by a qualified service technician
familiar with safety procedures and equipped with the proper tools and test instruments.
• Failure to carefully read and follow all instructions in this manual can result in equipment mal-
function, property damage, personal injury and/or death.
Installation
• Don’t use a power cord, a plug or a loose socket which is damaged.
- Otherwise, it may cause a fire or electrical shock.
• For electrical work, contact the dealer, seller, a qualified electrician, or an Authorized Service Center.
- Do not disassemble or repair the product. There is risk of fire or electric shock.
• Always ground the product.
- There is risk of fire or electric shock.
• Install the panel and the cover of control box securely.
- There is risk of fire or electric shock.
• Always install a dedicated circuit and breaker.
- Improper wiring or installation may cause fire or electric shock.
• Use the correctly rated breaker or fuse.
- There is risk of fire or electric shock.
• Do not modify or extend the power cable.
- There is risk of fire or electric shock.
• Do not let the air conditioner run for a long time when the humidity is very high and a door or a win-
dow is left open.
- Moisture may condense and wet or damage furniture.
• Be cautious when unpacking and installing the product.
- Sharp edges could cause injury. Be especially careful of the case edges and the fins on the con-
denser and evaporator.
• For installation, always contact the dealer or an Authorized Service Center.
- There is risk of fire, electric shock, explosion, or injury.
!
!
!
SAFETY PRECAUTIONS
ENGLISH
• Do not install the product on a defective installation stand.
- It may cause injury, accident, or damage to the product.
• Be sure the installation area does not deteriorate with age.
- If the base collapses, the air conditioner could fall with it, causing property damage, product failure,
and personal injury.
• There is a risk of fire and explosion.
- Inert gas (nitrogen) should be used when you check plumbing leaks, cleaning or repairs of pipes
etc.
If you are using combustible gases including oxygen, product may have the risk of fires and explo-
sions.
• Use a vacuum pump or Inert (nitrogen) gas when doing leakage test or air purge. Do not compress
air or Oxygen and do not use flammable gases. Otherwise, it may cause fire or explosion.
- There is the risk of death, injury, fire or explosion.
Operation
• Do not store or use flammable gas or combustibles near the product.
- There is risk of fire or failure of product.
CAUTION
Installation
• Always check for gas (refrigerant) leakage after installation or repair of product.
- Low refrigerant levels may cause failure of product.
• Install the drain hose to ensure that water is drained away properly.
- A bad connection may cause water leakage.
• Keep level even when installing the product.
- To avoid vibration or water leakage.
• Do not install the product where the noise or hot air from the outdoor unit could damage the neigh-
borhoods.
- It may cause a problem for your neighbors.
• Use two or more people to lift and transport the product.
- Avoid personal injury.
• Do not install the product where it will be exposed to sea wind (salt spray) directly.
- It may cause corrosion on the product. Corrosion, particularly on the condenser and evaporator
fins, could cause product malfunction or inefficient operation.
• Thickness of copper pipes used are as shown “Flaring work” Table.
- Never use copper pipes thinner than that in the table even when it is available on the market
• Do not use copper pipes having a collapsed.
- Otherwise, the expansion valve or capillary tube may become blocked with contaminants.
• For R410A model, use piping, flare nut and tools which is specified for R410A refrigerant.
- Using of (R22) piping, flare nut and tools may cause abnormally high pressure in the refrigerant
cycle (piping), and possibly result in explosion and injury.
• It is desirable that the amount of residual oil less than 40 mg/10m.
!
SAFETY PRECAUTIONS
4
ENGLISH
5
3 IMPORTANT SAFETY
INSTRUCTIONS
6 INSTALLATION PARTS
7 INSTALLATION TOOLS
7 INSTALLATION MAP
8 INSTALLATION
8 Select the best Location
8 Fixing Installation Plate
9 Drill a Hole in the Wall
9 Flaring Work
9 - Cut the pipes and the cable
9 - Burrs removal
9 - Putting nut on
9 - Flaring work
10 - Check
10 Connecting the Piping
10 - Good case
11 - Bad case
11 - Installation of Indoor Unit
11 - Piping
12 - Connecting the installation pipe and
drain hose to the indoor unit.
13 - Wrap the insulation material around
the connecting portion.
13 - Finishing the indoor unit installation
14 Checking the Drainage
14 - To check the drainage.
14 - Drain piping
15 Installation of filters
15 Test Running
15 - Prepare remote controller
TABLE OF CONTENTS
TABLE OF CONTENTS
ENGLISH
INSTALLATION TOOLS
6
INSTALLATION PARTS
ENGLISH
INSTALLATION PARTS
Name
Quantity Shape
Installation plate
1 EA
Type "A" screw
5 EA
Type "B" screw
2 EA
Type "C" screw
2 EA
Remote control
holder
1 EA
The feature can be changed according a type of model.
Screws for fixing panels are attached to decoration panel.
Figure FigureName
Screw driver
Electric drill
Measuring tape, Knife
Hole core drill
Spanner
Torque wrench
Multi-meter
Hexagonal wrench
Ammeter
Gas-leak detector
Thermometer,
Level
Flaring tool set
Name
INSTALLATION MAP
7
INSTALLATION MAP
Connecting cable
(Optional Parts)
Vinyl tape (Wide)
• Apply after carrying out a
drainage test.
• To carry out the drainage
test, remove the air filters
and pour water into the heat
exchanger.
Saddle
Gas side piping (Optional Parts)
Liquid side piping (Optional Parts)
Additional drain pipe
Vinyl tape (Narrow)
Drain Hose
Installation plate
Sleeve
Bushing-Sleeve
Putty(Gum Type Sealant)
Bend the pipe as closely
on the wall as possible,
but be careful that it
doesn't break.
NOTE
!
• You should purchase the installation parts.
* The feature can be changed according a type of model.
ENGLISH
Select the best Location
- There should not be any heat or steam near
the unit.
- Select a place where there are no obstacles
around of the unit.
- Make sure that condensation drainage can
be conveniently routed away.
- Do not install near a doorway.
- Ensure that the interval between a wall and
the left (or right) of the unit is more than
100mm. The unit should be installed as high
as possible on the wall, allowing a minimum
of 200mm from ceiling.
- Use a metal detector to locate studs to pre-
vent unnecessary damage to the wall.
* The feature can be changed according a
type of model.
Fixing Installation Plate
The wall you select should be strong and solid
enough to prevent vibration.
1
Before installation, confirm the position of a
screw between chassis and installation plate.
2 Mount the installation plate on the wall
with type "A" screws. If mounting the unit
on a concrete wall, use anchor bolts.
- Mount the installation plate horizontally
by aligning the centerline using Horizontal
meter .
3 Measure the wall and mark the centerline.
It is also important to use caution concern-
ing the location of the installation plate.
Routing of the wiring to power outlets is
through the walls typically. Drilling the hole
through the wall for piping connections
must be done safely.
More than 200
More than
100
More than 2300
More than
100
(Unit : mm)
CAUTION
Install the indoor unit on the wall where
the height from the floor is more than
2300mm.
!
Installation Plate
Chassis
Hook
Type "A" Screws
A-Type
B-Type
Ø65
217
175
Ø65
Ø65
Ø65
A Type : 442
B Type : 434
A Type : 442
B Type : 439
A Type : 133
B Type : 123
A Type : 95
B Type : 170
A Type B Type
Installation Plate
Installation Plate
Right rear piping
Left rear piping
Place a level on raised tab
Unit Outline
(Unit : mm)
Installation Plate
INSTALLATION
INSTALLATION
8
ENGLISH
Drill a Hole in the Wall
- Drill the piping hole with a ø65mm hole core
drill. Drill the piping hole at either the right or
the left with the hole slightly slanted to the
outdoor side.
Flaring Work
Main cause for gas leakage is due to defect of
flaring work. Carry out correct flaring work in
the following procedure.
Cut the pipes and the cable
1 Use the piping kit accessory or the pipes
purchased locally.
2 Measure the distance between the indoor
and the outdoor unit.
3 Cut the pipes a little longer than measured
distance.
4 Cut the cable 1.5m longer than the pipe
length.
Burrs removal
1. Completely remove all burrs from the cut
cross section of pipe/tube.
2. While removing burrs put the end of the
copper tube/pipe in a downward direction
while removing burrs location is also
changed in order to avoid dropping burrs
into the tubing.
Putting nut on
- Remove flare nuts attached to indoor and
outdoor unit, then put them on pipe/tube
having completed burr removal.
(not possible to put them on after finishing
flare work)
Flaring work
1 Firmly hold copper pipe in a bar with the di-
mension shown in below table table
below.
2 Carry out flaring work with the flaring tool.
5-7mm
(3/16"~5/16")
Indoor
WALL
Outdoor
Copper
pipe
90°
Slanted Uneven Rough
Pipe
Reamer
Point down
Flare nut
Copper tube
9
INSTALLATION
ENGLISH
Outside diameter A Thickness
mm inch mm mm
Ø6.35 1/4" 1.1~1.3 0.7
Ø9.52 3/8" 1.5~1.7 0.8
Ø12.7 1/2" 1.6~1.8 0.8
Ø15.88 5/8" 1.6~1.8 1.0
Ø19.05 3/4" 1.9~2.1 1.0
Bar
Copper pipe
Clamp handle
Red arrow mark
Cone
Yoke
Handle
Bar
"A"
Inclined
Inside is shiny without scratches
Smooth all round
Even length
all round
Surface
damaged
Cracked Uneven
thickness
= Improper flaring =
Check
1 Compare the flared work with the figure
by.
2 If a flared section is defective, cut it off
and do flaring work again.
Connecting the Piping
1 Pull the screw cap at the bottom of the in-
door unit
2 Remove the chassis cover from the unit by
loosing 2 screws
3 Pull back the tubing holder.
4 Remove pipe port cover and positioning
the tubing
* The feature can be changed according a
type of model.
Good case
- Press on the tubing cover and unfold the
tubing to downward slowly. And then bend
to the left side slowly.
Right
Indoor unit back side view
Tubing holder
Downwards
Left
Backwards
Chassis cover
INSTALLATION
10
ENGLISH
CAUTION
Installation Information. For right piping.
Follow the instruction above.
!
Bad case
- Following bending case from right to left di-
rectly may cause damage to the tubing.
* The feature can be changed according a
type of model.
Installation of Indoor Unit
1 Hook the indoor unit onto the upper por-
tion of the installation plate.( engage the
three hooks at the top of the indoor unit
with the upper edge of the installation
plate) Ensure that the hooks are properly
seated on the installation plate by moving
it left and right
2 Unlock the tubing holder from the chassis
and mount between the chassis and instal-
lation plate in order to separate the bottom
side of the indoor unit from the wall.
* The feature can be changed according a
type of model.
Piping
1 Insert the connecting cable through the
bottom side of indoor unit and connect the
cable (You can see detail contents in 'Con-
necting the cables' section)
<Left side piping>
View
Terminal block
Connecting cable
Remote controller
cable
Cable retainer
Installation plate
Tubing Holder
11
INSTALLATION
ENGLISH
Outside diameter
Torque
Indoor unit tubing Flare nut Pipes
<Right side piping>
2 Secure the cable onto the control board
with the cable retainer.
3 Tape the tubing pipe, drain hose and the
connection cable. Be sure that the drain
hose is located at the lowest side of the
bundle. Locating at the upper side can
cause overflow from the drain pan through
the inside of the unit.
<Left side piping>
<Right side piping>
* The feature can be changed according a
type of model.
Connecting the installation pipe
and drain hose to the indoor unit.
1 Align the center of the pipes and suffi-
ciently tighten the flare nut by hand
2 Tighten the flare nut with a wrench
3. When needed to extend the drain hose of
indoor unit, assembly the drain pipe as
shown on the drawing
mm inch kgf.m
Ø6.35 1/4 1.8~2.5
Ø9.52 3/8 3.4~4.2
Ø12.7 1/2 5.5~6.5
Ø15.88 5/8 6.3~8.2
Ø19.05 3/4 9.9~12.1
Wrench
Indoor unit tubing
Open-end wrench
(fixed)
Connection
pipe
Flare nut
Vinyl tape(narrow)
Adhesive
Drain pipe
Indoor unit drain hose
View
Terminal block
Connecting cable
Remote controller
cable
Cable retainer
Drain hose
Connecting pipe
Connecting
cable
Tape
Drain hose
Connecting pipe
Connecting
cable
Tape
Drain hose
INSTALLATION
12
ENGLISH
Wrap the insulation material
around the connecting portion.
1 Overlap the connection pipe insulation ma-
terial and the indoor unit pipe insulation
material. Bind them together with vinyl
tape so that there may be no gap.
2 Set the tubing cutting line upward.
Wrap the area which accommodates the
rear piping housing section with vinyl tape.
3 Bundle the piping and drain hose together
by wrapping them with vinyl tape sufficient
enough to cover where they fit into the
rear piping housing section.
Finishing the indoor unit
installation
1 Mount the tubing holder in the original
positon.
2 Ensure that the hooks are properly seated
on the installation plate by moving it left
and right.
3 Press the lower left and right sides of the
unit against the installation plate until the
hooks engage into their slots (clicking
sound).
4 Finish the assembly by screwing the unit
to the installation plate by using two
pieces of type "C" screws. And assemble a
chassis cover.
Insulation material
Gas Pipe
Liquid Pipe
Cutting Line
Cutting Line
Good Case Bad Case
* Tubing cutting line have to be upward.
Vinyl tape(narrow)
Connection pipe
Connecting cable
Vinyl tape (wide)
Wrap with vinyl tape
Indoor unit pipe
Pipe
Type 'C' screw
Wrap with vinyl tape
Drain hose
Pipe
Vinyl tape(wide)
13
INSTALLATION
ENGLISH
Checking the Drainage
To check the drainage.
1 Pour a glass of water on the evaporator.
2 Ensure the water flows through the drain
hose of the indoor unit without any leak-
age and goes out the drain exit.
Drain piping
1 The drain hose should point downward for
easy drain flow.
2 Do not make drain piping like the follow-
ing.
* The feature can be changed according a
type of model.
Drain pan
Drain
hose
Leakage
checking
Connecting area
drain hose
Leakage
checking
INSTALLATION
14
ENGLISH
Installation of filters
1 Pull out the [Allergy free filter + Triple Fil-
ter] from the separately packed plastic bag.
2 Detach the two nitto tapes from the filter.
3 Insert the filter into the filter case.
4 Detach two nitto tapes from the plasma fil-
ter.
* The feature can be changed according a
type of model.
Test Running
- Check that all tubing and wiring are properly
connected.
- Check that the gas and liquid side service
valves are fully open.
Prepare remote controller
1 Remove the battery cover by pulling it ac-
cording to the arrow direction.
2 Insert new batteries making sure that the
(+) and (–) of battery are installed correctly.
3 Reattach the cover by pushing it back into
position.
Allergy Free Filter +
Triple Filter (Optional)
Plasma Filter
NOTE
!
• Use 2 AAA(1.5volt) batteries. Do not use
rechargeable batteries.
Remove the batteries from the remote
controller if the system is not used for a
long time
15
INSTALLATION
ENGLISH
16
ENGLISH
www.lg.com
KURULUM KILAVUZU
KLİMA
• Lütfen ürünün kurulumunu yapmadan önce bu kılavuzu tamamen okuyun.
• Kurulum işi ulusal kablo tesisatı standartlarına göre ve yetkili kişiler tarafından
yapılmalıdır.
• Tamamen okuduktan sonra ileride de başvurmak için bu kurulum kılavuzunu
saklayın.
TIP : DUVARA MONTAJ
TÜRKÇE
İç mekanları aşırı derecede soğutmayın. Aksi takdirde sağğınıza zarar verebilir ve aşırı elektrik
tüketimine neden olabilir.
• Klimanızı çalıştırırken güneş ışınlarını jaluzi, stor perde veya normal perdeyle engelleyin.
• Klimanızı çalıştırırken kapıları ve pencereleri sıkı bir şekilde kapalı tutun.
İçerdeki havanın dolaşımı için hava akımının yönünü yatay veya dikey olarak ayarlayın.
İçerdeki havayı hızlı bir şekilde soğutmak veya ısıtmak için fanı kısa bir süre hızlandırın.
• Klima uzun süre kullanıldığı takdirde, içerideki havanın kalitesinde bozulma olabileceği için
havalandırma amacıyla pencereleri düzenli olarak açın.
• Hava filtresini 2 haftada bir temizleyin. Hava filtresinde biriken toz ve yabancı maddeler hava
akımını engelleyebilir veya soğutma/nem giderme işlevlerini zayıflatabilir.
Dikkat
Satın alma tarihini kanıtlama veya garanti amaçlarına yönelik olarak faturanızı bu sayfaya zımbalayın.
Model numarası ve seri numarasını buraya yazın:
Model numarası :
Seri numarası :
Her ünitenin kenarındaki bir etikette bu numaraları görebilirsiniz.
Bayii adı :
Satın alma tarihi :
Burada klimanızı kullanırken harcayacağınız enerjiyi azaltmak için bazı ipuçları bulunmaktadır.
Aşağıdaki talimatlara bakmak suretiyle klimanızı daha verimli kullanabilirsiniz:
ENERJİ TASARRUFUNA YÖNELİK İPUÇLARI
ENERJİ TASARRUFUNA YÖNELİK İPUÇLARI
2
TÜRKÇE
3
ÖNEMLİ GÜVENLİK TALİMATLARI
CİHAZI KULLANMADAN ÖNCE TÜM TALİMATLARI OKUYUN.
Tehlikeli durumlardan kaçınmak ve cihazınızda en yüksek performansını temin etmek için daima
aşağıda verilen talimatlara uyun
LG Electronics Ürünün uygun olmayan bir şekilde montajı veya kullanım rehberinin yanlış kullanıl-
ması nedeniyle yanlış çalışması veya hasar görmesinden sorumlu değildir.
UYARI
Talimatlar dikkate alınmadığında ciddi yaralanma veya ölüme neden olabilir
DIKKAT
Talimatlar dikkate alınmadığında küçük yaralanma veya ürün hasarına neden olabilir
UYARI
• Kalifiye olmayan kişiler tarafından yapılan montaj veya onarım işleri size ve diğer kişilere
tehlike yaratabilir.
• Montaj mutlaka yerel kanunlara; yerel kanunların olmadığı durumlarda, Ulusal Elektrik Kanunu
NFPA 70/ANSI C1-1003 veya mevcut baskısı ve Kanada Elektrik Kanunu Bölüm 1 CSA
C.22.1’e göre YAPILMALIDIR.
• Bu kılavuzdaki bilgiler güvenlik prosedürlerini bilen ve uygun alet ve test araçlarıyla donatılmış
kalifiye servis teknisyenlerinin kullanımına yöneliktir.
• Bu kılavuzdaki tüm talimatların dikkatlice okunmaması ve gözetilmemesi donanımda arızalara,
mal zararlarına, yaralanmaya ve/veya ölüme sebebiyet verebilir.
Kurulum
• Bir güç kablosu, fiş veya zarar görmüş gevşek bir yuvakullanmayın.
- Aksi takdirde, bir yangın veya elektrik çarpmasına neden olunabilir.
• Elektrik işleri için bayiye, satıcıya, ehliyetli bir elektrikçiye veya bir Yetkili Servis Merkezine başvurun.
- Ürünü sökmeyin veya tamir etmeyin. Yangın veya elektrik çarpması riski vardır.
• Ürünü daima topraklayın.
- Yangın veya elektrik çarpması riski vardır.
• Paneli ve denetim kutusunun kapağını sağlam bir şekilde kurun.
- Yangın veya elektrik çarpması riski vardır.
• Her zaman cihaz için özel çekilmiş devreyle kullanın.
- Hatalı kablo tesisatı veya kurulum yangın veya elektrik çarpmasına neden olabilir.
• Doğru oranlı şalter veya sigorta kullanın.
- Yangın veya elektrik çarpması riski vardır.
• Güç kablosunu modifiye etmeyin veya uzatmayın.
- Yangın veya elektrik çarpması riski vardır.
• Nem oranı çok yüksek iken ve bir kapı veya bir pencere açık bırakılmışsa klimayı çok uzun süre
çalıştırmayın.
- Nem yoğuşarak mobilyaları nemlendirebilir veya zarar verebilir.
• Ürünü ambalajından çıkarırken ve kurarken dikkatli olun.
- Keskin kenarlar yaralanmaya neden olabilir. Özellikle kasa kenarlarına ve yoğuşturucu ile buhar-
laştırıcının kanatlarına dikkat edin.
• Kurulum için her zaman bayiye veya bir Yetkili Servis Merkezine başvurun.
- Yangın, elektrik çarpması, patlama veya yaralanma riski vardır.
!
!
!
GÜVENLİK ÖNLEMLERİ
TÜRKÇE
• Ürünü kusurlu bir kurulum stendinin üzerine kurmayın.
- Bu, yaralanmaya, kazaya veya ürüne hasar verilmesine yol açabilir.
• Kurulum alanının zamanla kötüleşmeyeceğinden emin olun.
- Temeli düşerse klima da birlikte düşebilir, bu şekilde mülkiyete zarar verebilir, ürün arızalanabilir ve
kişisel yaralanmaya neden olabilir.
• Yangın veya patlama riski vardır.
- Dolgu kaçaklarını kontrol ederken, boruları temizlerken, onarırken vb durumlarda soy gaz (nitrojen)
kullanılmalıdır.
Oksijen de dahil olmak üzere yanıcı gazları kullanırsanız, üründe yangın çıkma ve patlama tehlikesi
vardır.
• Kaçak testi veya hava temizleme yaparken bir vakumlu pompa veya atıl (nitrojen) gazı kullanın.
Havayı veya oksijeni sıkıştırmayın ve alev alabilen gazları kullanmayın.
Aksi halde, yangına veya patlamaya sebep olabilir.
- Ölüm, yaralanma, yangın veya patlama riski vardır.
Çalışma
• Yanıcı gazları veya malzemeleri ürünün yanında muhafaza etmeyin veya kullanmayın.
- Yangın veya elektrik çarpması tehlikesi bulunmaktadır.
DİKKAT
Kurulum
• Ürünü kurduktan veya tamir ettikten sonra her zaman gaz (soğutucu sıvı) sızıntısı olup olmadığını
kontrol ediniz.
- Soğutucu sıvısı seviyesinin düşük olması ürünün arızalanmasına neden olabilir.
• Suyun doğru şekilde boşaltılmasını sağlamak için boşaltma hortumunu takın.
- Kötü bir bağlantı su sızıntısına neden olabilir.
• Ürünü kurarken düzgün tutun.
- Titreşimi veya su sızıntısını önlemek için.
• Ürünü, dış üniteden çıkan gürültü veya sıcak hava etrafı rahatsız etmeyecek yere kurun.
- Bu, komşularınız için sorun olabilir.
• Ürünü kaldırmak ve taşımak için iki veya daha fazla insan kullanın.
- Kişisel yaralanmayı önleyin.
• Ürünü deniz rüzgarına (tuz püskürmesine) doğrudan maruz kalacağı bir yere kurmayınız.
- Bu, ürünün paslanmasına neden olabilir. Özellikle yoğuşturucu ve buharlaştırıcı kanatlarının
korozyona uğraması ürünün arızalanmasına veya yetersiz çalışmasına neden olabilir.
• Kullanılan bakır boruların kalınlığı “Parlatma çalışması” Tablosunda gösterildiği gibidir.
- Piyasada bulunsa dahi tabloda belirtilenden daha ince bakır boruları asla kullanmayın.
• Çökmüş bakır boruları kullanmayın.
- Aksi halde, genişleme valfi veya kapiler boru kirler ile tıkanabilir.
• R410A modeli için, R410A soğutucusu için belirlenen boru, konik civata ve aletleri kullanın.
- (R22) borusunu, konik civatayı ve aletleri kullanmanız soğutma döngüsünde (boru) anormal yüksek
basınç oluşmasına sebep olabilir ve muhtemelen patlamaya ve yaralanmaya sebep olabilir.
• Kalıntı yağ miktarının 40 mg/10m değerinden daha düşük olması istenir.
!
GÜVENLİK ÖNLEMLERİ
4
TÜRKÇE
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33

LG AMNW09GDBR0 Yükleme Rehberi

Kategori
Split sistem klimalar
Tip
Yükleme Rehberi
Bu kılavuz aynı zamanda aşağıdakiler için de uygundur:

diğer dillerde