Acson A5LCY10FR Yükleme Rehberi

Kategori
Split sistem klimalar
Tip
Yükleme Rehberi

Bu kılavuz için de uygundur

INSTALLATION MANUAL
IM-5WMYJ-1110(0)-ACSON
Part No.:R08019035855
INVERTER WALL MOUNTED
SPLIT TYPE AIR CONDITIONER
(L Series)
Acson IM-WMJ-1110(0).indd 1Acson IM-WMJ-1110(0).indd 1 1/12/2011 6:24:46 PM1/12/2011 6:24:46 PM
Acson IM-WMJ-1110(0).indd 2Acson IM-WMJ-1110(0).indd 2 1/12/2011 6:24:48 PM1/12/2011 6:24:48 PM
1-1
h
s
i
l
g
nE
English
Indoor Unit [A5WMYL Series]
OUTLINE AND DIMENSIONS
A
B
C
H
I
B
F
E
J
G
G
L
D
B
K
M
A
F
A B C D E F G H I J K L M
800 288 206 166 184 42 46 55 56 154 182 263 52
Dimension
A5WMY10/15LR
THE MARK SHOWS PIPING DIRECTION
REAR REAR
LEFT RIGHT
TOP VIEW
BOTTOMBOTTOM
LOUVER FRONT GRILLE FIXED
SCREWS (INSIDE)
FRONT VIEW
SIGNAL RECEIVER
INDOOR UNIT
ON/OFF SWITCH
ROOM TEMPERATURE
THERMIRTOR (INSIDE)
SIDE VIEW
NAME PLATE
TERMINAL
BLOCK
WITH EARTH
TERMINAL
Use tape measure
as shown.
Position the end
of a tape measure
at
X
Recommended mounting
plate retention spots
(5 spots in all)
Liquid pipe end Gas pipe end
INSTALLATION PLATE All dimensions are in mm
Through the wall
hole Ø 65mm
Drain hose
position
Model
Original Instruction
Acson IM-WMJ-1110(0).indd Sec1:1Acson IM-WMJ-1110(0).indd Sec1:1 1/12/2011 6:24:48 PM1/12/2011 6:24:48 PM
1-2
Outdoor Unit [A5LCY10/15FR]
All dimensions are in mm
E
D
BC
IH
G
N
J
LK
F
A
ABCDEFGH I JKLMN
A5LCY10/15FR 550 658 51 11 273 16 14 470 96 299 94 60 14 133
Dimension
Model
Acson IM-WMJ-1110(0).indd Sec1:2Acson IM-WMJ-1110(0).indd Sec1:2 1/12/2011 6:24:48 PM1/12/2011 6:24:48 PM
1-3
h
s
i
l
g
nE
English
INSTALLATION MANUAL
This manual provides the procedures of installation to ensure a safe and good standard of operation for the air
conditioner unit.
Special adjustment may be necessary to suit local requirements.
Before using your air conditioner, please read this instruction manual carefully and keep it for future reference.
This appliance is intended to be used by expert or trained users in shops, in light industry and on farms, or for
commercial use by lay persons.
WARNING
• Installation and maintenance should be performed by
qualifi ed persons who are familiar with local code and
regulation, and experienced with this type of appliance.
• All fi eld wiring must be installed in accordance with the
national wiring regulation.
• Ensure that the rated voltage of the unit corresponds to
that of the name plate before commencing wiring work
according to the wiring diagram.
The unit must be GROUNDED to prevent possible hazard
due to insulation failure.
• All electrical wiring must not touch the refrigerant piping
or any moving parts of the fan motors.
Confi rm that the unit has been switched OFF before
installing or servicing the unit.
Disconnect from the main power supply before servicing
the air conditioner unit.
• DO NOT pull out the power cord when the power is ON.
This may cause serious electrical shocks which may
result in fi re hazards.
• Keep the indoor and outdoor units, power cable and
transmission wiring, at least 1m from TVs and radios, to
prevent distorted pictures and static. {Depending on the
type and source of the electrical waves, static may be
heard even when more than 1m away}.
CAUTION
Please take note of the following important points
when installing.
• Do not install the unit where leakage of fl ammable
gas may occur.
If gas leaks and accumulates around the unit, it
may cause fi re ignition.
Ensure that drainage piping is connected properly.
If the drainage piping is not connected properly, it
may cause water leakage which will dampen the
furniture.
Do not overcharge the unit.
This unit is factory pre-charged. Overcharge will
cause over-current or damage to the compressor.
Ensure that the unit’s panel is closed after service or
installation.
Unsecured panels will cause the unit to operate
noisily.
Sharp edges and coil surfaces are potential locations
which may cause injury hazards. Avoid from being in
contact with these places.
Before turning off the power supply, set the remote
controller’s ON/OFF switch to the “OFF” position to
prevent the nuisance tripping of the unit. If this is not
done, the unit’s fans will start turning automatically when
power resumes, posing a hazard to service personnel or
the user.
Do not install the units at or near doorway.
Do not operate any heating apparatus too close to the
air conditioner unit or use in room where mineral oil, oil
vapour or oil steam exist, this may cause plastic part to
melt or deform as a result of excessive heat or chemical
reaction.
When the unit is used in kitchen, keep fl our away from
going into suction of the unit.
This unit is not suitable for factory used where cutting oil
mist or iron powder exist or voltage fl uctuates greatly.
• Do not install the units at area like hot spring or oil
refi nery plant where sulphide gas exists.
Ensure the color of wires of the outdoor unit and the
terminal markings are same to the indoors respectively.
IMPORTANT : DO NOT INSTALL OR USE THE AIR
CONDITIONER UNIT IN A LAUNDRY ROOM.
Do not use joined and twisted wires for incoming power
supply.
• For any enquiries on spare part, please contact your
authorized dealer.
The equipment is not intended for use in a potentially
explosive atmosphere.
SAFETY PRECAUTIONS
NOTICE
Disposal requirements
Your air conditioning product is marked with this symbol. This means that electrical and electronic products shall not
be mixed with unsorted household waste.
Do not try to dismantle the system yourself: the dismantling of the air conditioning system, treatment of the refrigerant,
of oil and of other parts must be done by a qualifi ed installer in accordance with relevant local and national legislation.
Air conditioners must be treated at a specialized treatment facility for re-use, recycling and recovery. By ensuring this
product is disposed of correctly, you will help to prevent potential negative consequences for the environment and
human health. Please contact the installer or local authority for more information.
Batteries must be removed from the remote controller and disposed of separately in accordance with relevant local
and national legislation.
Acson IM-WMJ-1110(0).indd Sec1:3Acson IM-WMJ-1110(0).indd Sec1:3 1/12/2011 6:24:49 PM1/12/2011 6:24:49 PM
1-4
IMPORTANT
Important information regarding the refrigerant used
This product contains fl uorinated greenhouse gases covered by the Kyoto Protocol.
Do not vent gases into the atmosphere.
Refrigerant type: R410A
GWP
(1)
value: 1975
(1)
GWP = global warming potential
Please fi ll in with indelible ink,
A the factory refrigerant charge of the product,
B the additional refrigerant amount charged in the fi eld and
A + B the total refrigerant charge
on the refrigerant charge label supplied with the product.
The fi lled out label must be adhered in the proximity of the product charging port (e.g. onto the inside of the service
cover).
1 factory refrigerant charge of the product:
see unit name plate
(2)
2 additional refrigerant amount charged in the fi eld
3 total refrigerant charge
4 contains fl uorinated greenhouse gases covered by the Kyoto Protocol
5 outdoor unit
6 refrigerant cylinder and manifold for charging
(2)
In case of multiple indoor systems, only 1 label must be adhered*, mentioning the total factory refrigerant charge of
all indoor units connected in the refrigerant system.
Periodical inspections for refrigerant leaks may be required depending on European or local legislation. Please
contact your local dealer for more information.
* on the outdoor unit
Acson IM-WMJ-1110(0).indd Sec1:4Acson IM-WMJ-1110(0).indd Sec1:4 1/12/2011 6:24:49 PM1/12/2011 6:24:49 PM
1-5
h
s
i
l
g
nE
English
INSTALLATION DIAGRAM
.
INSTALLATION OF THE OUTDOOR UNIT
Where a wall or other obstacle is in the path of outdoor unit’s intake or exhaust airflow, follow the installation guidelines below.
• For any of the below installation patterns, the wall height on the exhaust side should be 1200mm or less.
n 50ahteroM n 50ahteroM
More than 150
More than
100
More than 50 More than 100
Side view
1200
or less
Wall facing one side Walls facing two sides
Top view
Top view
unit: mm
More than 150
More than 300
More than 50
Walls facing three sides
Indoor Unit
30mm or more from ceiling
Front Panel
50mm or more from walls
(on both sides)
Air fi lter
Outdoor Unit
Caulk pipe
hole gap
with putty.
Cut thermal insulation pipe to
an appropriate length and wrap
it with tape, making sure that no
gap is left in the insulation pipe’s
cut line.
Wrap the insulation pipe with the
nishing tape from bottom to top.
Service lid
• Opening service lid
Service lid is opening/closing
type.
• Opening method
1) Remove the service lid
screws.
2) Pull out the service lid
diagonally down in the direction
of the arrow.
3) Pull down.
250mm from wall
M4 X 12L
Acson IM-WMJ-1110(0).indd Sec1:5Acson IM-WMJ-1110(0).indd Sec1:5 1/12/2011 6:24:49 PM1/12/2011 6:24:49 PM
1-6
Drain work. (Heat Pump Unit Only)
1) Use drain plug for drainage.
2) If the drain port is covered by a mounting base or fl oor surface, place
additional foot bases of at least 30mm in height under the outdoor unit’s
feet.
3) In cold areas, do not use a drain hose with the outdoor unit.
(Otherwise, drain water may freeze, impairing heating performance.)
INSTALLATION OF THE INDOOR UNIT
The indoor unit must be installed in such a way so as to
prevent short circuit of the cool discharged air with the hot
return air. Please follow the installation clearance shown
in the fi gure. Do not place the indoor unit where there
could be direct sunlight shining on it. Also, this location
must be suitable for piping and drainage, and be away
from doors or windows.
The refrigerant piping can be routed to the unit in a
number of ways (left or right from the back of the unit), by
using the cut-out holes on the casing of the unit.
Bend the pipes carefully to the required position in order
to align it with the holes. For the side and bottom out,
hold the bottom of the piping and then position it to the
required direction. The condensation drain hose can be
taped to the pipes.
All dimensions are in mm
Drain water hole
Bottom frame
Drain plug
Hose (available commercially,
inner dia. 16mm)
Air fl ow
(Indoor)
min. 50 min. 50
(Space for
maintenance)
(Space for
maintenance)
Required space
min. 30
(Space for
performance)
Right-side, right-back or right-bottom piping
Remove pipe port cover
here for right-side piping
Remove pipe port cover
here for right-bottom piping
Bind coolant pipe and
drain hose together
with insulating tape.
Left-side, left-back or left-bottom piping
Right-side
piping
Right-back piping
Left-back piping
Left-side piping
Left-bottom piping
Remove pipe port cover
here for left-side piping
Remove pipe port cover here for left-bottom
piping
Right-bottom
piping
Acson IM-WMJ-1110(0).indd Sec1:6Acson IM-WMJ-1110(0).indd Sec1:6 1/12/2011 6:24:49 PM1/12/2011 6:24:49 PM
1-7
h
s
i
l
g
nE
English
Mounting Installation Plate
Ensure that the wall is strong enough to withstand the
weight of the unit. Otherwise, it is necessary to reinforce
the wall with plates, beams or pillars.
Use the level gauge for horizontal mounting, and fi x it
with 5 suitable screws.
In case the rear piping draws out, drill a hole 65mm in
diameter with a cone drill, slightly lower on the outside
wall (see fi gure).
166
184
181.7
55.554.5
153.8
263
51.9
800
9
.5
4
2
.2
4
882
2.24
9.54
Recommended Mounting Plate Retention Spots And
Dimensions
Mount The Unit Onto The Installation Plate
Hook the indoor unit onto the upper portion of the
installation plate (Engage the two hooks at the rear top
of the indoor unit with the upper edge of the installation
plate). Ensure that the hooks are properly seated on the
installation plate by moving it to the left and right.
How To Attach The Indoor Unit
Hook the claws of the bottom frame to the mounting
plate.
How To Remove The Indoor Unit
Push up the marked area (at the lower part of the front
grille) to release the claws.
Water Drainage Piping
The indoor drain pipe must be in a downward gradient for
smooth drainage. Avoid situations that are likely to cause
water to leak.
Do not install the unit at altitude over 2000m for both
indoor & outdoor.
CAUTION
Mounting plate
xing screw
Mounting plate
Mounting plate
Clip
Mark (Rear side)
Bottom frame
Front grille
When stripping the ends
of interconnecting wires in
advance, bind right ends
of wires with insulating
tape.
Mounting plate
Hand indoor unit’s hook here.
Wire guide
Interconnecting
wires
Water Drainage
Correct Wrong Wrong Wrong
Water
Leaking
Water
Leaking
Water
Leaking
Water
Retention
End
dipped
into
water
Drain
Recommended mounting plate
retention spots (5 spots in all)
Use tape measure as shown.
Position the end of a tape
measure at
X
Through
the wall
hole
Ø 65mm
Drain
hose
position
Gas pipe endLiquid pipe end
All dimensions are in mm
Hole with cone drill
Wall embedded pipe
(Field supply)
Caulking
OutsideInside
Ø 65
Wall embedded pipe
(Field supply)
Wall hole cover
(Field supply)
Acson IM-WMJ-1110(0).indd Sec1:7Acson IM-WMJ-1110(0).indd Sec1:7 1/12/2011 6:24:49 PM1/12/2011 6:24:49 PM
1-8
REFRIGERANT PIPING
Allowable Piping Length
If the pipe is too long, both the capacity and reliability of
the unit will drop. As the number of bends increases,
resistance to the fl ow of refrigerant system increases, thus
lowering cooling capacity. As a result, the compressor
may become defective. Always choose the shortest path
and follow the recommendations as tabulated below:
Model
Min. Allowable Length, m
Max. Allowable Length, m
Additional charge of refrigerant
Max. Allowable Elevation, m
Gas Pipe Size, mm/(in)
Liquid Pipe Size
, mm/(in)
10 15
3
15
20
10
9.52 (3/8")
6.35 (1/4")
*Be sure to add the proper amount of additional refrigerant.
Failure to do so may result in reduced performance.
Remark: The refrigerant pre-charged in the outdoor
unit is for piping length up to 7.5m.
Piping Works and Flaring technique
Do not use contaminated or damaged copper tubing. If
any piping, evaporator or condenser had been exposed
or had been opened for 15 seconds or more, the system
must be vacuumed. Generally do not remove plastic,
rubber plugs and brass nuts from the valves, fi ttings,
tubing and coils until it is ready to connect suction or
liquid line into valves or fi ttings.
If any brazing work is required, ensure that nitrogen
gas is passed through coil and joints while the brazing
work is being done. This will eliminate soot formation
on the inside wall of copper tubings.
Cut the pipe stages by stages, advancing the blade of
pipe cutter slowly. Extra force and a deep cut will cause
more distortion of pipe and therefore extra burr. See
Figure A.
Remove burrs from cut edges of the pipes with remover.
See Figure B. Hold the pipe on top position and burr
removel at lower position to prevent metal chips from
entering the pipe. This will avoid unevenness on the
are faces which will cause gas leak.
• Insert the fl are nuts, mounted on the connection parts
of both the indoor unit and outdoor unit, into the copper
pipes.
The exact length of pipe protruding from the top surface
of the swaging block is determined by the fl aring tool.
See Figure C.
Fix the pipe fi rmly on the swaging block. Match the
centers of both the swaging block and the fl aring punch,
then tighten the fl aring punch fully.
The refrigerant pipe connection are insulated by closed
cell polyurethane.
Piping Connection To The Units
• Align the center of the piping and tighten the fl are nut
suffi ciently with fi ngers. See Figure D.
Finally, tighten the fl are nut with torque wrench until the
wrench clicks.
• When tightening the fl are nut with the torque wrench,
ensure that the tightening direction follows the arrow
indicated on the wrench.
The refrigerant pipe connection are insulated by closed
cell polyurethane.
Pipe Size, mm (in) Torque, Nm / (ft-Ib)
6.35 (1/4") 18 (13.3)
9.52 (3/8") 42 (31.0)
12.70 (1/2") 55 (40.6)
15.88 (5/8") 65 (48.0)
19.05 (3/4") 78 (57.6)
Ø Tube, D A (mm)
Inch mm Imperial
(Wing-nut Type)
Rigid
(Clutch Type)
1/4" 6.35 1.3 0.7
3/8" 9.52 1.6 1.0
1/2" 12.70 1.9 1.3
5/8" 15.88 2.2 1.7
3/4" 19.05 2.5 2.0
Figure A
Figure B
Figure C
Figure D
Flared Tube
Flare Joint
Flare Nut
Indoor Piping
Torque Wrench
Spanar
Copper Tube
Swaging Block
1/4t
Cutting Copper Tube
Remove Burr
A
D
Acson IM-WMJ-1110(0).indd Sec1:8Acson IM-WMJ-1110(0).indd Sec1:8 1/12/2011 6:24:50 PM1/12/2011 6:24:50 PM
1-9
h
s
i
l
g
nE
English
ELECTRICAL WIRING CONNECTION
IMPORTANT :* The fi gures shown in the table are for information purpose only. They should be checked and
selected to comply with the local/national codes of regulations. This is also subject to the type of
installation and conductors used.
** The appropriate voltage range should be checked with label data on the unit.
All wires must be fi rmly connected.
Make sure all the wire do not touch the refrigerant pipings, compressor or any moving parts.
The connecting wire between the indoor unit and the outdoor unit must be clamped by using provided cord
anchorage.
The power supply cord must be equivalent to H07RN-F which is the minimum requirement.
Make sure no external pressure is applied to the terminal connectors and wires.
Make sure all the covers are properly fi xed to avoid any gap.
Use round crimp-style terminal for connecting wires to the power supply terminal block. Connect the wires by
matching to the indication on terminal block. (Refer to the wiring diagram attached on the unit.)
* If the length of the cable is more than 2m, use cable
with bigger size.
1
2
SIG
N
L
2
1
SIG
Indoor Unit
Terminal Block
Outdoor Unit
Terminal Block
Power Supply
Cable
There must be an all pole disconnection
in the supply mains with a contact
seperation of at least 3mm.
Model 10
Voltage range**
Power supply cable size* mm²
Number of core
Interconnection cable size* mm²
Number of core
Recommended time delay fuse A
1.5
3
1.5
4
15
15
1.5
3
1.5
4
15
220V - 240V / 1Ph / 50Hz+
Used the correct screwdriver for terminal screws tightening. Unsuitable screwdrivers can damage the screw head.
Over tightening can damage the terminal screws.
Do not connect wire of different gauge to same terminal.
Keep wiring in an orderly manner. Prevent the wiring from obstructing other parts and the terminal box cover.
Attach insulation sleeve
Round crimp-style terminal
Electric wire
Connect wires of the
same gauge to both side.
Do not connect wires of the
same gauge to one side.
Do not connect wires
of different gauges.
Acson IM-WMJ-1110(0).indd Sec1:9Acson IM-WMJ-1110(0).indd Sec1:9 1/12/2011 6:24:50 PM1/12/2011 6:24:50 PM
1-10
SPECIAL PRECAUTIONS WHEN DEALING WITH R410A UNIT
R410A is a new HFC refrigerant which does not damage
the ozone layer. The working pressure of this new
refrigerant is 1.6 times higher than conventional refriger-
ant (R22), thus proper installation / servicing is essential.
Never use refrigerant other than R410A in an air
conditioner which is designed to operate with R410A.
POE or PVE oil is used as lubricant for R410A
compressor, which is different from the mineral oil used
for R22 compressor. During installation or servicing,
extra precaution must be taken not to expose the
R410A system too long to moist air. Residual POE or
PVE oil in the piping and components can absorb
moisture from the air.
To prevent mischarging, the diameter of the service
port on the flare valve is different from that of R22.
Use tools and materials exclusively for refrigerant
R410A. Tools exclusively for R410A are manifold valve,
charging hose, pressure gauge, gas leak detector, flare
tools, torque wrench, vacuum pump and refrigerant
cylinder.
As an R410A air conditioner incurs higher pressure
than R22 units, it is essential to choose the copper
pipes correctly. Never use copper pipes thinner than
0.8mm even though they are available in the market.
If the refrigerant gas leakage occurs during installation /
servicing, be sure to ventilate fully. If the refrigerant gas
comes into contact with fire, a poisonous gas may
occur.
When installing or removing an air conditioner, do not
allow air or moisture to remain in the refrigerant cycle.
Refrigerant Piping
Outdoor Unit 3 ways valve
Allen key
Service Port
Flare nut
HIGH PRESSURE GAUGE
GAUGE MANIFOLD
LOW PRESSURE GAUGE
HANDLE HI (ALWAYS CLOSED)
CHARGE HOSE
-760mmHg
HANDLE LO
CHARGE HOSE
VACUUM PUMP
ADAPTER FOR
COUNTER FLOW
PREVENTION
CHECK VALVE
LIQUID VALVE
HIGH PRESSURE GAUGE
LOW PRESSURE GAUGE
GAUGE MANIFOLD
-760mmHg
HANDLE LO
HANDLE HI (ALWAYS CLOSED)
CHARGE HOSE
CHARGE HOSE
CHECK VALVE
LIQUID VALVE
GAS VALVE
(3-WAY)
CONFIGURATION OF AIR
PURGE BY CHARGING
CONFIGURATION OF AIR
PURGE BY CHARGING
GAS VALVE
(3-WAY)
Vacuuming The Piping And The Indoor Unit
Vacuuming is necessary to eliminate all moisture and air from the system.
VACUUMING AND CHARGING
Except for the outdoor unit which is pre-charged with
refrigerant, the indoor unit and the refrigerant connection
pipes must be air-purged because the air containing
moisture that remains in the refrigerant cycle may cause
malfunction of the compressor.
Remove the caps from the valve and the service port.
Connect the center of the charging gauge to the
vacuum pump.
Connect the charging gauge to the service port of the
3-way valve.
Start the vacuum pump. Evacuate for approximately 30
minutes. The evacuation time varies with different
vacuum pump capacity. Confirm that the charging
gauge needle has moved towards -760mmHg.
Caution
If the gauge needle does not move to -760mmHg, be
sure to check for gas leaks (using the refrigerant
detector) at flare type connection of the indoor and
outdoor unit and repair the leak before proceeding to
the next step.
Close the valve of the changing gauge and stop the
vacuum pump.
On the outdoor unit, open the suction valve (3 way)
and liquid valve (2 way) (in anti-clockwise direction)
with 4mm key for hexagon sacked screw.
Charge Operation
This operation must be done by using a gas cylinder and
a precise weighing machine. The additional charge is
topped-up into the outdoor unit using the suction valve via
the service port.
Remove the service port cap.
Connect the low pressure side of the charging gauge to
the suction service port center of the cylinder tank and
close the high pressure side of the gauge. Purge the air
from the service hose.
Start the air conditioner unit.
Open the gas cylinder and low pressure charging valve.
When the required refrigerant quantity is pumped into
the unit, close the low pressure side and the gas
cylinder valve.
Disconnect the service hose from service port. Put back
the service port cap.
Acson IM-WMJ-1110(0).indd Sec1:10Acson IM-WMJ-1110(0).indd Sec1:10 1/12/2011 6:24:51 PM1/12/2011 6:24:51 PM
1-11
h
s
i
l
g
nE
English
INDICATOR LIGHTS
IR Signal Receiver
When an infrared remote control operating signal has
been transmitted, the signal receiver on the indoor unit
will respond as below to confi rm acceptance of the signal
transmission.
ON to OFF
OFF to ON
Pump down / Cool force on
Others
1 Long Beep
2 Short Beep
1 Short Beep
Cooling Unit / Heat Pump Unit
The table shows the LED indicator lights for the air
conditioner unit under normal operation and fault
conditions. The LED indicator lights are located at the
side of the air conditioner unit.
The heat pump units are equipped with an “auto” mode
sensor whereby it will provide reasonable room
temperature by switching automatically to either “cool”
or “heat” mode according to the temperature set by the
user.
LED Indicator Lights for Cooling Unit / Heat Pump
Unit
LED Indicator Lights : Normal Operation & Fault Condition For Cooling / Heat Pump Unit
COOL/HEAT
(GREEN/RED)
GREEN
GREEN
GREEN
GREEN
RED
RED
RED
Operation
Cool mode
Heat mode
Auto mode in Heating operation
Auto mode in Cooling operation
Timer on
Sleep mode on
Fan mode on
Dry mode on
Defrost operation
ON
Blinking
IR Receiver
Cool / Heat
Timer
Sleep
ON/OFF switch
GREEN
Unit error
IR Receiver
Acson IM-WMJ-1110(0).indd Sec1:11Acson IM-WMJ-1110(0).indd Sec1:11 1/12/2011 6:24:52 PM1/12/2011 6:24:52 PM
1-12
OPERATING RANGE
COOLING HEATING
INDOOR TEMP. (°CWB) INDOOR TEMP. (°CDB)
DB: Dry bulb WB: Wet bulb
AIR FILTER
1. Open the front panel.
• Hold the panel at the recesses on the main unit (2
recesses on right and left sides) and lift it until it
stops.
2. Pull out the air fi lters.
• Push a little upwards the tab at the center of each
air lter, then pull it down.
3. Clean or replace each fi lter.
When shaking off remaining water, do not wring the
lter.
4. Set the air fi lter and close the front panel.
• Insert claws of the fi lters into slots of the front panel.
Close the front panel slowly and push the panel at
the 3 points. (1 on each side and 1 in the middle.)
The air fi lter have a symmetrical form in the horizontal
direction.
FRONT
Process on
main unit
OUTDOOR TEMP. (°CDB)
OUTDOOR TEMP. (°CWB)
Acson IM-WMJ-1110(0).indd Sec1:12Acson IM-WMJ-1110(0).indd Sec1:12 1/12/2011 6:24:52 PM1/12/2011 6:24:52 PM
1-13
h
s
i
l
g
nE
English
SERVICE AND MAINTENANCE
Service Parts
Indoor air fi lter
Indoor unit
Maintenance Procedures Period
1. Remove any dust adhering to the fi lter by using a vacuum cleaner or wash in
lukewarm water (below 40°C/104°F) with a neutral cleaning detergent.
2. Rinse the fi lter well and dry before placing it back onto the unit.
3. Do not use gasoline, volatile substances or chemicals to clean the fi lter.
1. Clean any dirt or dust on the grille or panel by wiping it with a soft cloth
soaked in lukewarm water (below 40°C/104°F) and a neutral detergent
solution.
2. Do not use gasoline, volatile substances or chemicals to clean the indoor
unit.
At least once every 2
weeks.
More frequently if
necessary.
At least once every 2
weeks.
More frequently if
necessary.
Recess on
main unit
Rotating
shaft
1. Open the front panel.
Hold the panel at the recesses on the main unit (2
recesses on right and left sides) and lift it until it
stops.
2. Remove the front panel.
• While lifting the front panel further, slide it to the right
and pull it to the front side. The left rotating shaft is
detached. Slide the right rotating shaft to the left and
pull it to the front side to remove it.
3. Attach the front panel.
Align the right and left rotating shafts of the front
panel with the grooves and push them all the way
in.
Gently close the front panel. (Push both ends and
the center on the front panel.)
Do not touch the metal parts of the indoor unit. It may cause an injury.
When removing or attaching the front panel, support the panel securely with hand to prevent it from falling.
• For cleansing, do not use hot water above 40°C, benzine, gasoline, thinner, nor other volatile oils, polishing
compound, scrubbing brushes, nor other hand stuff.
• After cleaning, make sure that the front panel is securely fi xed.
CAUTION
When The Unit Is Not To Be Used For An Extended Long Period Of Time
Operate the unit for 2 hours
with the following setting.
Operating mode : cool
Temperature : 30°C/86°F
Remove the power plug.
If you are using an independent
electric circuit for your unit, cut
off the circuit.
Remove the batteries in the
remote control.
• Avoid direct contact of any coil treatment cleaners on plastic part. This may cause plastic part to deform as a
result of chemical reaction.
CAUTION
Acson IM-WMJ-1110(0).indd Sec1:13Acson IM-WMJ-1110(0).indd Sec1:13 1/12/2011 6:24:52 PM1/12/2011 6:24:52 PM
1-14
MEMO
Acson IM-WMJ-1110(0).indd Sec1:14Acson IM-WMJ-1110(0).indd Sec1:14 1/12/2011 6:24:52 PM1/12/2011 6:24:52 PM
1-15
h
s
i
l
g
nE
English
MEMO
Acson IM-WMJ-1110(0).indd Sec1:15Acson IM-WMJ-1110(0).indd Sec1:15 1/12/2011 6:24:52 PM1/12/2011 6:24:52 PM
1-16
MEMO
Acson IM-WMJ-1110(0).indd Sec1:16Acson IM-WMJ-1110(0).indd Sec1:16 1/12/2011 6:24:52 PM1/12/2011 6:24:52 PM
hs
i
l
g
nE
Italiano
2-1
H
I
F
E
J
G
G
L
D
B
K
M
A
F
A
B
C
B
Unità Interna [Serie A5WMYL]
DISEGNI E DIMENSIONI
IL SEGNO MOSTRA LA DIREZIONE DEI TUBI
Dimensioni
Modello
ABCDEFGHI JKL M
A5WMY10/15LR 800 288 206 166 184 42 46 55 56 154 182 263 52
Istruzioni originali
DIETRO DIETRO
SINISTRA DESTRA
VISTA DALL’ALTO
IN
BASSO
IN
BASSO
FERITOIA DI
AERAZIONE
VITI INSERITE NELLA GRIGLIA
FRONTALE (ALL’INTERNO)
VISTA FRONTALE
RICEVITORE DI
SEGNALE
UNITÀ INTERNA
INTERRUTTORE ON/OFF
TEMPERATURA
AMBIENTE TERMISTORE
(ALL’INTERNO)
VISTA LATERALE
PIASTRA
MORSETTIERA
CON TERMINALE
A TERRA
Usare la misura del nastro
come posizione che indica
la fi ne del nastro a
Punti di ritenzione raccomandati
per la piastra di montaggio
(5 punti in tutto)
Estremità del tubo del liquido Estremità del tubo del gas
LASTRA DI INSTALLAZIONE Tutte le dimensioni sono in mm
Foro nel muro di
Ø 65mm
Posizione del
tubo di scarico
Acson IM-WMJ-0111(0)_IT.indd 1Acson IM-WMJ-0111(0)_IT.indd 1 1/12/2011 12:02:31 PM1/12/2011 12:02:31 PM
2-2
Unità Esterna [Serie A5LCY10/15FR]
Dimensioni
Modello
ABCDEFGH I J KLMN
A5LCY10/15FR 550 658 51 11 273 16 14 470 96 299 94 60 14 133
E
D
B C
IH
G
N
J
LK
F
A
Tutte le dimensioni sono in mm
Acson IM-WMJ-0111(0)_IT.indd 2Acson IM-WMJ-0111(0)_IT.indd 2 1/12/2011 12:02:32 PM1/12/2011 12:02:32 PM
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116
  • Page 117 117
  • Page 118 118
  • Page 119 119
  • Page 120 120

Acson A5LCY10FR Yükleme Rehberi

Kategori
Split sistem klimalar
Tip
Yükleme Rehberi
Bu kılavuz için de uygundur